Catalogue / Hydrogen sensors & safety systems

No photo yet

Catalytic bead hydrogen gas detector, Ultra 2 seriesSample

by Airavattek Hydrogen (Sample) · verified by BARREL

Price for verified buyers

Ordered and invoiced through BARREL — one contract, one GST invoice.

Customise and request quote

Made to order: change the marked specification rows to what you need; Airavattek Hydrogen (Sample) quotes for it.

Or send an open RFQ to every matching merchant.

Register your company to see prices.

Catalytic bead hydrogen gas detector from Airavattek, Ultra 2 series: 3 detection range options between 0-4% vol and 0-100% vol. Key features: local display with calibration, interface with plant ESD and self-diagnostics and sensor fault alarm. Used by h2 refuelling stations, battery rooms and refineries. Designed and tested to IEC 60079-29-1, IEC 60079-0 and IEC 61508 (SIL 2). Lead time 6-8 weeks; delivers to South India. Sample listing: illustrative data for testing BARREL Shop, not a real offer.

Brand
Airavattek
Model
AIR-AB5 series
Listing type
Product
Unit
nos
Minimum order
10 nos
Lead time
6-8 weeks
Warranty
12 months
Standards
IEC 60079-29-1, IEC 60079-0, IEC 61508 (SIL 2)
Delivers to
South India
GST rate
18 %
Country of origin
India
Packaging
Drum / reel with end caps
Delivery terms
Door delivery in metro cities
Returns
Returns within 15 days if unused, in original packing
Other terms
Sample data for testing; not a real offer.

Variants

VariantSpecificationsMin. order · lead timePrice, ex GST
Detection range0-4% volAIR-AB5-01Detection range: 0-4% vol10 nos · 6-8 weeksfor verified buyers
Detection range0-100% LELAIR-AB5-02Detection range: 0-100% LEL10 nos · 6-8 weeksfor verified buyers
Detection range0-100% volAIR-AB5-03Detection range: 0-100% vol10 nos · 6-8 weeksfor verified buyers

Specifications

Detection range0-4% vol to 0-100% vol (see variants)
Sensor typeCatalytic beadmade to order: Electrochemical / Thermal conductivity / Semiconductor
OutputRelaymade to order: 4-20 mA HART / Modbus RTU
Response time T90< 30 smade to order: < 10 s
Accuracy+/- 5% of FSmade to order: +/- 2% of FS
Hazardous areaEx ia IIC T4
Supply24 V DC
Ingress protectionIP65
HousingAluminiummade to order: SS 316
Operating temperature-40 to 70 deg C
Calibration interval6 monthsmade to order: 12 months
Alarm set points10% LEL
Sensor life5 yearsmade to order: 3 years

BARREL: Bharat Atom Renewable Resources Energy Limited