Transformer nitrogen injection fire prevention and extinguishing system (NIFPS), Edge seriesSample
by Aravalijal Fire Protection (Sample) · verified by BARREL
Price for verified buyers
Ordered and invoiced through BARREL — one contract, one GST invoice.
Customise and request quoteMade to order: change the marked specification rows to what you need; Aravalijal Fire Protection (Sample) quotes for it.
Or send an open RFQ to every matching merchant.
Register your company to see prices.
The Edge range of transformer nitrogen injection fire prevention and extinguishing system (NIFPS) by Aravalijal covers 5 transformer oil volume options (Up to 10 kL to 60-100 kL). Design: rapid oil drain depressurises tank, fully automatic with manual override and nitrogen blankets and cools oil to extinguish fire. Used by reactors in EHV yards, generator transformers at plants and power transformers at substations. Designed and tested to IS 3034, CBIP Manual on Transformers and CEA Safety Regulations 2023. Lead time 12-16 weeks; delivers to All India. Sample listing: illustrative data for testing BARREL Shop, not a real offer.
- Brand
- Aravalijal
- Model
- ARA-578 series
- Listing type
- Product
- Unit
- set
- Minimum order
- 5 set
- Lead time
- 12-16 weeks
- Warranty
- 36 months from commissioning
- Standards
- IS 3034, CBIP Manual on Transformers, CEA Safety Regulations 2023
- Delivers to
- All India
- GST rate
- 18 %
- Country of origin
- India
- Packaging
- Drum / reel with end caps
- Delivery terms
- FOR site, freight included
- Returns
- Returns within 15 days if unused, in original packing
- Other terms
- Sample data for testing; not a real offer.
Variants
| Variant | Specifications | Min. order · lead time | Price, ex GST |
|---|---|---|---|
| Transformer oil volumeUp to 10 kLARA-578-01 | Transformer oil volume: Up to 10 kL | 5 set · 12-16 weeks | for verified buyers |
| Transformer oil volume10-20 kLARA-578-02 | Transformer oil volume: 10-20 kL | 5 set · 12-16 weeks | for verified buyers |
| Transformer oil volume20-40 kLARA-578-03 | Transformer oil volume: 20-40 kL | 5 set · 12-16 weeks | for verified buyers |
| Transformer oil volume40-60 kLARA-578-04 | Transformer oil volume: 40-60 kL | 5 set · 12-16 weeks | for verified buyers |
| Transformer oil volume60-100 kLARA-578-05 | Transformer oil volume: 60-100 kL | 5 set · 12-16 weeks | for verified buyers |
Specifications
| Transformer oil volume | Up to 10 kL to 60-100 kL (see variants) |
|---|---|
| Principle | Nitrogen injection and drain |
| Nitrogen cylinders | 5 x 68 Lmade to order: 3 x 68 L / 8 x 68 L |
| Operating pressure | 150 bar |
| Oil drain valve | Pneumatic |
| Detection | Differential relay + Buchholz + heat detector |
| Control | PLC-based cubicle with hot standby |
| Response time | Within 30 seconds |
| Oil drain depth | Top 10% of the tank oil |
| Power supply | 110 VDCmade to order: 24 VDC with backup battery |
| Ex-vent | Included |
| Communication | Hardwired to SCADAmade to order: IEC 60870-5-104 |
| Isolation | Cable gland and cubicle IP55 |