Catalogue / Compact secondary substations
Compact secondary substation, Xtra 8 seriesSample
by Coorgswarna Transformers (Sample) · verified by BARREL
Price for verified buyers
Ordered and invoiced through BARREL — one contract, one GST invoice.
Customise and request quoteMade to order: change the marked specification rows to what you need; Coorgswarna Transformers (Sample) quotes for it.
Or send an open RFQ to every matching merchant.
Register your company to see prices.
Coorgswarna Xtra 8 compact secondary substation, offered in 3 transformer rating options from 250 kVA to 630 kVA. Design: heat dissipation tested, quick site installation and internal arc proof design. Typically used for housing complexes, solar power plants and industrial parks. Designed and tested to IEC 62271-202, IS 1180 and IEC 62271-200. Lead time 10-14 weeks; delivers to All India. Sample listing: illustrative data for testing BARREL Shop, not a real offer.
- Brand
- Coorgswarna
- Model
- COO-116 series
- Listing type
- Product
- Unit
- nos
- Minimum order
- 1 nos
- Lead time
- 10-14 weeks
- Warranty
- 24 months
- Standards
- IEC 62271-202, IS 1180, IEC 62271-200
- Delivers to
- All India
- GST rate
- 18 %
- Country of origin
- India
- Packaging
- Steel skid with shrink wrap
- Delivery terms
- FOR nearest railhead
- Returns
- Replacement of items damaged in transit within 7 days
- Other terms
- Sample data for testing; not a real offer.
Variants
| Variant | Specifications | Min. order · lead time | Price, ex GST |
|---|---|---|---|
| Transformer rating250 kVACOO-116-01 | Transformer rating: 250 kVA | 1 nos · 10-14 weeks | for verified buyers |
| Transformer rating500 kVACOO-116-02 | Transformer rating: 500 kVA | 1 nos · 10-14 weeks | for verified buyers |
| Transformer rating630 kVACOO-116-03 | Transformer rating: 630 kVA | 1 nos · 10-14 weeks | for verified buyers |
Specifications
| Transformer rating | 250 kVA to 630 kVA (see variants) |
|---|---|
| Primary voltage | 11 kVmade to order: 22 kV / 33 kV |
| Secondary voltage | 0.433 kV |
| HV equipment | VCB panel |
| Transformer type | Oil-immersed |
| LT section | MCCB feedersmade to order: ACB incomer |
| Enclosure | Concrete |
| Ingress protection | IP54 |
| Internal arc rating | 16 kA 1 s |
| Short-circuit rating | 20 kAmade to order: 25 kA |
| Metering | Multifunction meter, CT operated |
| Ventilation | Forced fan |
| Oil containment | Integrated sump |