Coorgswarna Plus dry-type transformer with enclosure IP23, offered in 3 rating options from 1600 kVA to 5000 kVA. Key features: suitable for indoor and building use, temperature scanner with fan control and anti-vibration pads. Used by data centres, high-rise buildings and wind turbine nacelles. Designed and tested to IS 11171, IEC 60076-11 and IS 2026. Lead time 8-10 weeks; delivers to All India. Sample listing: illustrative data for testing BARREL Shop, not a real offer.
- Brand
- Coorgswarna
- Model
- COO-0E1 series
- Listing type
- Product
- Unit
- nos
- Minimum order
- 5 nos
- Lead time
- 8-10 weeks
- Warranty
- 36 months
- Standards
- IS 11171, IEC 60076-11, IS 2026
- Delivers to
- All India
- GST rate
- 18 %
- Country of origin
- India
- Packaging
- Steel skid with shrink wrap
- Delivery terms
- FOR nearest railhead
- Returns
- Returns within 15 days if unused, in original packing
- Other terms
- Sample data for testing; not a real offer.
Variants
| Variant | Specifications | Min. order · lead time | Price, ex GST |
|---|---|---|---|
| Rating1600 kVACOO-0E1-01 | Rating: 1600 kVA | 5 nos · 8-10 weeks | on quote |
| Rating2500 kVACOO-0E1-02 | Rating: 2500 kVA | 5 nos · 8-10 weeks | on quote |
| Rating5000 kVACOO-0E1-03 | Rating: 5000 kVA | 5 nos · 8-10 weeks | on quote |
Specifications
| Rating | 1600 kVA to 5000 kVA (see variants) |
|---|---|
| Voltage ratio | 22/0.433 kVmade to order: 11/0.433 kV / 33/0.433 kV |
| Technology | Cast resin |
| Insulation class | Class H |
| Cooling | ANmade to order: AN/AF |
| Winding material | Copper |
| Impedance | 6%made to order: 4% |
| Vector group | Dyn11 |
| Enclosure | IP00made to order: IP23 / IP31 |
| Tap changer | Off-circuit +/- 5% |
| Partial discharge | < 10 pC |
| Protection | PT100 sensors with relay |
| Fire behaviour | F1 / E2 / C2 |