The Neo 2 range of dry-type transformer with enclosure IP23 by Ellora covers 5 rating options (100 kVA to 1600 kVA). Key features: temperature scanner with fan control, maintenance-free with no oil and low noise. Typically used for data centres, high-rise buildings and wind turbine nacelles. Designed and tested to IS 11171, IEC 60076-11 and IS 2026. Lead time 4-6 weeks; delivers to East & North-East India. Sample listing: illustrative data for testing BARREL Shop, not a real offer.
- Brand
- Ellora
- Model
- ELL-0E3 series
- Listing type
- Product
- Unit
- nos
- Minimum order
- 1 nos
- Lead time
- 4-6 weeks
- Warranty
- 24 months
- Standards
- IS 11171, IEC 60076-11, IS 2026
- Delivers to
- East & North-East India
- GST rate
- 18 %
- Country of origin
- India
- Packaging
- As per item, transit-safe
- Delivery terms
- FOR site, freight included
- Returns
- No returns on made-to-order items
- Other terms
- Sample data for testing; not a real offer.
Variants
| Variant | Specifications | Min. order · lead time | Price, ex GST |
|---|---|---|---|
| Rating100 kVAELL-0E3-01 | Rating: 100 kVA | 1 nos · 4-6 weeks | for verified buyers |
| Rating250 kVAELL-0E3-02 | Rating: 250 kVA | 1 nos · 4-6 weeks | for verified buyers |
| Rating500 kVAELL-0E3-03 | Rating: 500 kVA | 1 nos · 4-6 weeks | for verified buyers |
| Rating1000 kVAELL-0E3-04 | Rating: 1000 kVA | 1 nos · 8-10 weeks | for verified buyers |
| Rating1600 kVAELL-0E3-05 | Rating: 1600 kVA | 1 nos · 8-10 weeks | for verified buyers |
Specifications
| Rating | 100 kVA to 1600 kVA (see variants) |
|---|---|
| Voltage ratio | 22/0.433 kVmade to order: 11/0.433 kV / 33/0.433 kV |
| Technology | VPI |
| Insulation class | Class Hmade to order: Class F |
| Cooling | AN |
| Winding material | Aluminiummade to order: Copper |
| Impedance | 6%made to order: 4% |
| Vector group | Dyn11 |
| Enclosure | IP31made to order: IP00 / IP23 |
| Tap changer | Off-circuit +/- 5% |
| Partial discharge | < 10 pC |
| Protection | PT100 sensors with relay |
| Fire behaviour | F1 / E2 / C2 |