Transformer nitrogen injection fire prevention and extinguishing system (NIFPS), Xtra seriesSample
by Jhelumfaraday Fire Engineers (Sample) · verified by BARREL
Price for verified buyers
Ordered and invoiced through BARREL — one contract, one GST invoice.
Customise and request quoteMade to order: change the marked specification rows to what you need; Jhelumfaraday Fire Engineers (Sample) quotes for it.
Or send an open RFQ to every matching merchant.
Register your company to see prices.
The Xtra range of transformer nitrogen injection fire prevention and extinguishing system (NIFPS) by Jhelumfaraday covers 3 transformer oil volume options (10-20 kL to 40-60 kL). Key features: control cubicle with status indication to SCADA, rapid oil drain depressurises tank and auto-trip on protection signal and explosion vent flow. Suited to reactors in EHV yards, generator transformers at plants and power transformers at substations. Designed and tested to IS 3034, CBIP Manual on Transformers and CEA Safety Regulations 2023. Lead time 12-16 weeks; delivers to All India and export (SAARC, Middle East, Africa). Sample listing: illustrative data for testing BARREL Shop, not a real offer.
- Brand
- Jhelumfaraday
- Model
- JHE-571 series
- Listing type
- Product
- Unit
- set
- Minimum order
- 1 set
- Lead time
- 12-16 weeks
- Warranty
- 36 months from commissioning
- Standards
- IS 3034, CBIP Manual on Transformers, CEA Safety Regulations 2023
- Delivers to
- All India and export (SAARC, Middle East, Africa)
- GST rate
- 18 %
- Country of origin
- India
- Packaging
- Drum / reel with end caps
- Delivery terms
- FOR site, freight included
- Returns
- Replacement of items damaged in transit within 7 days
- Other terms
- Sample data for testing; not a real offer.
Variants
| Variant | Specifications | Min. order · lead time | Price, ex GST |
|---|---|---|---|
| Transformer oil volume10-20 kLJHE-571-01 | Transformer oil volume: 10-20 kL | 1 set · 12-16 weeks | for verified buyers |
| Transformer oil volume20-40 kLJHE-571-02 | Transformer oil volume: 20-40 kL | 1 set · 12-16 weeks | for verified buyers |
| Transformer oil volume40-60 kLJHE-571-03 | Transformer oil volume: 40-60 kL | 1 set · 12-16 weeks | for verified buyers |
Specifications
| Transformer oil volume | 10-20 kL to 40-60 kL (see variants) |
|---|---|
| Principle | Nitrogen injection and drain |
| Nitrogen cylinders | 5 x 68 L |
| Operating pressure | 150 bar |
| Oil drain valve | Pneumatic |
| Detection | Differential relay + Buchholz + heat detector |
| Control | PLC-based cubicle with hot standby |
| Response time | Within 30 seconds |
| Oil drain depth | Top 10% of the tank oil |
| Power supply | 24 VDC with backup batterymade to order: 110 VDC |
| Ex-vent | Included |
| Communication | Hardwired to SCADAmade to order: IEC 60870-5-104 |
| Isolation | Cable gland and cubicle IP55 |