Catalogue / SF6 circuit breakers

No photo yet

SF6 dead tank circuit breaker, Eco 2 seriesSample

by Jhelum Switchgear (Sample) · verified by BARREL

Price for verified buyers

Ordered and invoiced through BARREL — one contract, one GST invoice.

Customise and request quote

Made to order: change the marked specification rows to what you need; Jhelum Switchgear (Sample) quotes for it.

Or send an open RFQ to every matching merchant.

Register your company to see prices.

Jhelum Eco 2 SF6 dead tank circuit breaker, offered in 3 system voltage options from 72.5 kV to 245 kV. Design: point-on-wave controller option, corrosion-proof control cabinet and density monitor with two stage alarm. Suited to transmission lines, renewable pooling stations and industrial EHV supply. Designed and tested to IEC 62271-100, IS 13118 and IEC 62271-1. Lead time 12-16 weeks; delivers to All India. Sample listing: illustrative data for testing BARREL Shop, not a real offer.

Brand
Jhelum
Model
JHE-EB4 series
Listing type
Product
Unit
nos
Minimum order
5 nos
Lead time
12-16 weeks
Warranty
30 months from supply
Standards
IEC 62271-100, IS 13118, IEC 62271-1
Delivers to
All India
GST rate
18 %
Country of origin
India
Packaging
Steel skid with shrink wrap
Delivery terms
Ex-works, freight extra at actuals
Returns
Returns within 15 days if unused, in original packing
Other terms
Sample data for testing; not a real offer.

Variants

VariantSpecificationsMin. order · lead timePrice, ex GST
System voltage72.5 kVJHE-EB4-01System voltage: 72.5 kV5 nos · 12-16 weeksfor verified buyers
System voltage145 kVJHE-EB4-02System voltage: 145 kV5 nos · 12-16 weeksfor verified buyers
System voltage245 kVJHE-EB4-03System voltage: 245 kV5 nos · 12-16 weeksfor verified buyers

Specifications

System voltage72.5 kV to 245 kV (see variants)
Rated current3150 Amade to order: 1250 A / 2000 A / 4000 A
Breaking current40 kA
Operating mechanismSpring-springmade to order: Hydraulic spring
OperationSingle-polemade to order: 3-pole
InterrupterTwo breaks
SF6 pressure0.6 MPa abs
Duty cycleO-0.3s-CO-3min-CO
Close time< 100 ms
InsulatorPorcelain
Auxiliary supply220 V DC
Creepage25 mm/kV
Mechanical enduranceM2

BARREL: Bharat Atom Renewable Resources Energy Limited