Catalogue / Ring main units (RMU)
11 kV ring main unit, Ultra 3 seriesSample
by Kavachtek Switchboards (Sample) · verified by BARREL
Price for verified buyers
Ordered and invoiced through BARREL — one contract, one GST invoice.
Customise and request quoteMade to order: change the marked specification rows to what you need; Kavachtek Switchboards (Sample) quotes for it.
Or send an open RFQ to every matching merchant.
Register your company to see prices.
The Ultra 3 range of 11 kV ring main unit by Kavachtek covers 4 configuration options (2-way (LBS+LBS) to 4-way (2LBS+LBS+VCB)). Key features: cable test facility on front panel, internal arc tested for operator safety and optional SCADA-ready motor operators and FPI. Used by urban 11 kV ring networks, discom compact substations and residential and commercial campuses. Designed and tested to IEC 62271-200, IEC 62271-103 and IEC 62271-105. Lead time 4-6 weeks; delivers to South India. Sample listing: illustrative data for testing BARREL Shop, not a real offer.
- Brand
- Kavachtek
- Model
- KAV-EC9 series
- Listing type
- Product
- Unit
- nos
- Minimum order
- 1 nos
- Lead time
- 4-6 weeks
- Warranty
- 24 months from supply
- Standards
- IEC 62271-200, IEC 62271-103, IEC 62271-105
- Delivers to
- South India
- GST rate
- 18 %
- Country of origin
- India (imported sub-assemblies)
- Packaging
- As per item, transit-safe
- Delivery terms
- FOR nearest railhead
- Returns
- No returns on made-to-order items
- Other terms
- Sample data for testing; not a real offer.
Variants
| Variant | Specifications | Min. order · lead time | Price, ex GST |
|---|---|---|---|
| Configuration2-way (LBS+LBS)KAV-EC9-01 | Configuration: 2-way (LBS+LBS) | 1 nos · 4-6 weeks | for verified buyers |
| Configuration3-way (LBS+LBS+TF)KAV-EC9-02 | Configuration: 3-way (LBS+LBS+TF) | 1 nos · 4-6 weeks | for verified buyers |
| Configuration3-way (LBS+LBS+VCB)KAV-EC9-03 | Configuration: 3-way (LBS+LBS+VCB) | 1 nos · 8-12 weeks | for verified buyers |
| Configuration4-way (2LBS+LBS+VCB)KAV-EC9-04 | Configuration: 4-way (2LBS+LBS+VCB) | 1 nos · 8-12 weeks | for verified buyers |
Specifications
| Configuration | 2-way (LBS+LBS) to 4-way (2LBS+LBS+VCB) (see variants) |
|---|---|
| Rated voltage | 12 kVmade to order: 24 kV / 36 kV |
| Rated current - ring | 630 A |
| Transformer feeder | 200 A fuse-switch |
| Short-circuit rating | 16 kA/3 s |
| Insulation medium | SF6 gas |
| Switch type | Three-position load-break |
| Extensibility | Extensible one side |
| Protection relay | Numerical relaymade to order: Self-powered O/C-E/F relay |
| Fault passage indicator | Includedmade to order: Optional |
| Enclosure | Mild steel RAL 7035 |
| Degree of protection | IP67 tank |
| Motor operator | Not fittedmade to order: Optional on ring switches |