The Pro 3 range of thermal conductivity hydrogen analyser by Kaverihertz covers 4 detection range options (0-1000 ppm to 0-100% vol). Design: remote calibration support, hot swap sensor head and ATEX / IECEx flameproof enclosure. Used by refineries, h2 refuelling stations and battery rooms. Designed and tested to IEC 60079-29-1, IEC 60079-0 and IEC 61508 (SIL 2). Lead time 6-8 weeks; delivers to All India. Sample listing: illustrative data for testing BARREL Shop, not a real offer.
- Brand
- Kaverihertz
- Model
- KAV-E47 series
- Listing type
- Product
- Unit
- nos
- Minimum order
- 1 nos
- Lead time
- 6-8 weeks
- Warranty
- 24 months
- Standards
- IEC 60079-29-1, IEC 60079-0, IEC 61508 (SIL 2)
- Delivers to
- All India
- GST rate
- 18 %
- Country of origin
- India
- Packaging
- Steel skid with shrink wrap
- Delivery terms
- FOR nearest railhead
- Returns
- Replacement of items damaged in transit within 7 days
- Other terms
- Sample data for testing; not a real offer.
Variants
| Variant | Specifications | Min. order · lead time | Price, ex GST |
|---|---|---|---|
| Detection range0-1000 ppmKAV-E47-01 | Detection range: 0-1000 ppm | 1 nos · 6-8 weeks | for verified buyers |
| Detection range0-4% volKAV-E47-02 | Detection range: 0-4% vol | 1 nos · 6-8 weeks | for verified buyers |
| Detection range0-100% LELKAV-E47-03 | Detection range: 0-100% LEL | 1 nos · 6-8 weeks | for verified buyers |
| Detection range0-100% volKAV-E47-04 | Detection range: 0-100% vol | 1 nos · 6-8 weeks | for verified buyers |
Specifications
| Detection range | 0-1000 ppm to 0-100% vol (see variants) |
|---|---|
| Sensor type | Catalytic beadmade to order: Electrochemical / Thermal conductivity / Semiconductor |
| Output | Relaymade to order: 4-20 mA HART / Modbus RTU |
| Response time T90 | < 10 smade to order: < 30 s |
| Accuracy | +/- 2% of FSmade to order: +/- 5% of FS |
| Hazardous area | Ex ia IIC T4 |
| Supply | 24 V DC |
| Ingress protection | IP66made to order: IP65 |
| Housing | SS 316 |
| Operating temperature | -40 to 70 deg C |
| Calibration interval | 6 monthsmade to order: 12 months |
| Alarm set points | 10% LELmade to order: 20% LEL |
| Sensor life | 3 years |