Catalogue / Transformer overhaul & oil filtration

No photo yet

Bushing and OLTC replacement, Core 4 seriesSample

by Kaveriohm Infra Services (Sample) · verified by BARREL

Price for verified buyers

Ordered and invoiced through BARREL — one contract, one GST invoice.

Customise and request quote

Made to order: change the marked specification rows to what you need; Kaveriohm Infra Services (Sample) quotes for it.

Or send an open RFQ to every matching merchant.

Register your company to see prices.

Bushing and OLTC replacement from Kaveriohm, Core 4 series: 4 transformer rating options between 5 MVA and 50 MVA. Key features: post-work tan delta and ratio tests, oil sampling and DGA before work and hot oil circulation under vacuum. Typically used for solar and wind pooling substations, state utility asset life extension and industrial distribution transformers. Delivered in line with IS 335 (Mineral Insulating Oil), IS 1866 (Oil Maintenance) and IEC 60422. Mobilisation Mobilisation in 3-5 days; serves All India. Sample listing: illustrative data for testing BARREL Shop, not a real offer.

Brand
Kaveriohm
Model
KAV-619 series
Listing type
Service
Unit
nos
Minimum order
1 nos
Lead time
Mobilisation in 3-5 days
Warranty
Oil quality guarantee 6 months
Standards
IS 335 (Mineral Insulating Oil), IS 1866 (Oil Maintenance), IEC 60422
Delivers to
All India
GST rate
18 %
Country of origin
India
Delivery terms
Site mobilisation as per work order
Returns
Re-work of defective scope at no cost
Other terms
Sample data for testing; not a real offer.

Variants

VariantSpecificationsMin. order · lead timePrice, ex GST
Transformer rating5 MVAKAV-619-01Transformer rating: 5 MVA1 nos · Mobilisation in 3-5 daysfor verified buyers
Transformer rating10 MVAKAV-619-02Transformer rating: 10 MVA1 nos · Mobilisation in 3-5 daysfor verified buyers
Transformer rating20 MVAKAV-619-03Transformer rating: 20 MVA1 nos · Planned shutdown requiredfor verified buyers
Transformer rating50 MVAKAV-619-04Transformer rating: 50 MVA1 nos · Planned shutdown requiredfor verified buyers

Specifications

Transformer rating5 MVA to 50 MVA (see variants)
ServiceFull overhaul with rewinding
Filtration machineMobile 12000 L/hrmade to order: Vacuum dehydration 6000 L/hr
Oil BDV targetAbove 60 kV
Moisture targetBelow 10 ppmmade to order: Below 5 ppm
TestingDGA, furan, BDV, tan delta
SparesBushings and OLTC parts at cost
Downtime5-7 days
Site workHot oil circulation at sitemade to order: Workshop repair
Crew4 technicians with supervisor
CertificateOverhaul report with test datamade to order: Oil test report from NABL lab

BARREL: Bharat Atom Renewable Resources Energy Limited