Catalogue / Hydrant & sprinkler systems
Hydrant landing valve and hose cabinet, Ultra 5 seriesSample
by Konarkakshay Fire Protection (Sample) · verified by BARREL
Price for verified buyers
Ordered and invoiced through BARREL — one contract, one GST invoice.
Customise and request quoteMade to order: change the marked specification rows to what you need; Konarkakshay Fire Protection (Sample) quotes for it.
Or send an open RFQ to every matching merchant.
Register your company to see prices.
Konarkakshay Ultra 5 hydrant landing valve and hose cabinet, offered in 3 pump capacity options from 410 m³/h at 88 m to 684 m³/h at 88 m. Highlights: 100% diesel standby for power failure, complete system with piping, hydrants and hoses and jockey pump maintains line pressure. Suited to warehouses and industrial buildings, transformer yards and solar and BESS facilities. Designed and tested to IS 3844, IS 15105 and IS 12469. Lead time 6-8 weeks; delivers to All India. Sample listing: illustrative data for testing BARREL Shop, not a real offer.
- Brand
- Konarkakshay
- Model
- KON-5E1 series
- Listing type
- Product
- Unit
- lot
- Minimum order
- 10 lot
- Lead time
- 6-8 weeks
- Warranty
- 12 months from commissioning
- Standards
- IS 3844, IS 15105, IS 12469
- Delivers to
- All India
- GST rate
- 18 %
- Country of origin
- India
- Packaging
- Drum / reel with end caps
- Delivery terms
- Door delivery in metro cities
- Returns
- No returns on made-to-order items
- Other terms
- Sample data for testing; not a real offer.
Variants
| Variant | Specifications | Min. order · lead time | Price, ex GST |
|---|---|---|---|
| Pump capacity410 m³/h at 88 mKON-5E1-01 | Pump capacity: 410 m³/h at 88 m | 10 lot · 6-8 weeks | for verified buyers |
| Pump capacity546 m³/h at 88 mKON-5E1-02 | Pump capacity: 546 m³/h at 88 m | 10 lot · 6-8 weeks | for verified buyers |
| Pump capacity684 m³/h at 88 mKON-5E1-03 | Pump capacity: 684 m³/h at 88 m | 10 lot · 6-8 weeks | for verified buyers |
Specifications
| Pump capacity | 410 m³/h at 88 m to 684 m³/h at 88 m (see variants) |
|---|---|
| Pump type | Horizontal split-case |
| Drivers | Diesel enginemade to order: Electric motor |
| Jockey pump | 10.8 m³/h at 88 m |
| Pipe | MS Class C with epoxy paint |
| Valves | Gate/butterfly NRV |
| Hydrant type | Landing valve internal |
| Hose | 63 mm RRL type A |
| Panel | Auto start-stop with pressure switches |
| Storage | Underground RCC tank |
| Sprinkler | Quartzoid bulb 68 °C |
| Standby | Diesel engine 100% |
| Approvals | TAC / UL-FM listed pumps |