Catalogue / MV metal-clad switchboards (11–33 kV)
Indoor MV switchgear panel with VCB, Xtra seriesSample
by Krishnaprithvi Switchgear (Sample) · verified by BARREL
Price on quote
Ordered and invoiced through BARREL — one contract, one GST invoice.
Customise and request quoteMade to order: change the marked specification rows to what you need; Krishnaprithvi Switchgear (Sample) quotes for it.
Or send an open RFQ to every matching merchant.
The Xtra range of indoor MV switchgear panel with VCB by Krishnaprithvi covers 4 rating options (11 kV 1250 A to 33 kV 1250 A). Key features: type test reports from recognised labs, test facility for cable tests without isolating and earthing switch interlocked with breaker. Suited to steel and cement plants, renewable plant evacuation boards and grid substations 33/11 kV. Designed and tested to IEC 62271-200, IEC 62271-100 and IS 3427. Lead time 12-16 weeks; delivers to All India. Sample listing: illustrative data for testing BARREL Shop, not a real offer.
- Brand
- Krishnaprithvi
- Model
- KRI-B86 series
- Listing type
- Product
- Unit
- nos
- Minimum order
- 1 nos
- Lead time
- 12-16 weeks
- Warranty
- 18 months from commissioning
- Standards
- IEC 62271-200, IEC 62271-100, IS 3427
- Delivers to
- All India
- GST rate
- 18 %
- Country of origin
- India
- Packaging
- Steel skid with shrink wrap
- Delivery terms
- FOR site, freight included
- Returns
- Replacement of items damaged in transit within 7 days
- Other terms
- Sample data for testing; not a real offer.
Variants
| Variant | Specifications | Min. order · lead time | Price, ex GST |
|---|---|---|---|
| Rating11 kV 1250 AKRI-B86-01 | Rating: 11 kV 1250 A | 1 nos · 12-16 weeks | on quote |
| Rating11 kV 2500 AKRI-B86-02 | Rating: 11 kV 2500 A | 1 nos · 12-16 weeks | on quote |
| Rating22 kV 1250 AKRI-B86-03 | Rating: 22 kV 1250 A | 1 nos · 12-16 weeks | on quote |
| Rating33 kV 1250 AKRI-B86-04 | Rating: 33 kV 1250 A | 1 nos · 12-16 weeks | on quote |
Specifications
| Rating | 11 kV 1250 A to 33 kV 1250 A (see variants) |
|---|---|
| Insulation | Air-insulated |
| Short-circuit rating | 25 kA/3 smade to order: 31.5 kA/3 s / 40 kA/3 s |
| Panel function | Capacitor bank feedermade to order: Incomer / Bus coupler / Outgoing feeder |
| Busbar | Double busbarmade to order: Single busbar |
| Internal arc rating | IAC AFLR 40 kA 1 s |
| Loss of service continuity | LSC2Bmade to order: LSC2A |
| Partition class | PM metallic partition |
| Auxiliary supply | 220 V DC |
| Protection relays | Directional O/C |
| Communication | IEC 60870-5-103made to order: IEC 61850 / Modbus RTU |
| Bus VT | Fixed |
| Degree of protection | IP4X |