Catalogue / Station batteries (Ni-Cd, VRLA)

No photo yet

Ni-Cd pocket plate battery bank, Core seriesSample

by Shivalik Protection Systems (Sample) · verified by BARREL

Price for verified buyers

Ordered and invoiced through BARREL — one contract, one GST invoice.

Customise and request quote

Made to order: change the marked specification rows to what you need; Shivalik Protection Systems (Sample) quotes for it.

Or send an open RFQ to every matching merchant.

Register your company to see prices.

The Core range of ni-Cd pocket plate battery bank by Shivalik covers 4 capacity options (300 Ah to 1000 Ah). Highlights: long float life in hot ambient, documentation for capacity test and includes rack and inter-cell links. Typically used for switchyard DC systems, EHV substations and power plants. Designed and tested to IS 10918, IS 1651 and IEC 60623. Lead time 3-4 weeks; delivers to All India. Sample listing: illustrative data for testing BARREL Shop, not a real offer.

Brand
Shivalik
Model
SHI-ED8 series
Listing type
Product
Unit
nos
Minimum order
1 nos
Lead time
3-4 weeks
Warranty
24 months
Standards
IS 10918, IS 1651, IEC 60623
Delivers to
All India
GST rate
18 %
Country of origin
India
Packaging
As per item, transit-safe
Delivery terms
Ex-works, freight extra at actuals
Returns
Returns within 15 days if unused, in original packing
Other terms
Sample data for testing; not a real offer.

Variants

VariantSpecificationsMin. order · lead timePrice, ex GST
Capacity300 AhSHI-ED8-01Capacity: 300 Ah1 nos · 3-4 weeksfor verified buyers
Capacity500 AhSHI-ED8-02Capacity: 500 Ah1 nos · 3-4 weeksfor verified buyers
Capacity800 AhSHI-ED8-03Capacity: 800 Ah1 nos · 6-8 weeksfor verified buyers
Capacity1000 AhSHI-ED8-04Capacity: 1000 Ah1 nos · 6-8 weeksfor verified buyers

Specifications

Capacity300 Ah to 1000 Ah (see variants)
ChemistryFlooded lead-acidmade to order: Ni-Cd / VRLA gel
Nominal cell voltage1.2 Vmade to order: 2 V
Number of cells86
Bank voltage220 V
Discharge rateC10made to order: C5
Design life15 yearsmade to order: 20 years / 25 years
ContainerSAN
Operating temperature-20 to 50 deg C
RackEpoxy-painted steel
ElectrolyteDilute H2SO4
Float charge2.25 V per cellmade to order: 1.42 V per cell
MaintenanceLowmade to order: Maintenance free