Catalogue / Power conversion systems (PCS)
Bidirectional power conversion system for BESS, Core seriesSample
by Taxila Batteries (Sample) · verified by BARREL
Price for verified buyers
Ordered and invoiced through BARREL — one contract, one GST invoice.
Customise and request quoteMade to order: change the marked specification rows to what you need; Taxila Batteries (Sample) quotes for it.
Or send an open RFQ to every matching merchant.
Register your company to see prices.
Taxila Core bidirectional power conversion system for BESS, offered in 4 rated power options from 50 kW to 500 kW. Design: seamless on-grid to off-grid transition, remote firmware update and ride-through for voltage and frequency events. Used by frequency regulation, microgrid and DG sync and solar firming. Designed and tested to IEC 62477-1, IEC 62109-1 and IEEE 1547. Lead time 8-10 weeks; delivers to All India. Sample listing: illustrative data for testing BARREL Shop, not a real offer.
- Brand
- Taxila
- Model
- TAX-5E2 series
- Listing type
- Product
- Unit
- nos
- Minimum order
- 1 nos
- Lead time
- 8-10 weeks
- Warranty
- 5 years standard
- Standards
- IEC 62477-1, IEC 62109-1, IEEE 1547
- Delivers to
- All India
- GST rate
- 18 %
- Country of origin
- India (imported sub-assemblies)
- Packaging
- Corrugated box on pallet
- Delivery terms
- Ex-works, freight extra at actuals
- Returns
- Replacement of items damaged in transit within 7 days
- Other terms
- Sample data for testing; not a real offer.
Variants
| Variant | Specifications | Min. order · lead time | Price, ex GST |
|---|---|---|---|
| Rated power50 kWTAX-5E2-01 | Rated power: 50 kW | 1 nos · 8-10 weeks | for verified buyers |
| Rated power100 kWTAX-5E2-02 | Rated power: 100 kW | 1 nos · 8-10 weeks | for verified buyers |
| Rated power250 kWTAX-5E2-03 | Rated power: 250 kW | 1 nos · 8-10 weeks | for verified buyers |
| Rated power500 kWTAX-5E2-04 | Rated power: 500 kW | 1 nos · 8-10 weeks | for verified buyers |
Specifications
| Rated power | 50 kW to 500 kW (see variants) |
|---|---|
| DC voltage range | 700-1200 V |
| AC output voltage | 400 Vmade to order: 690 V / 800 V |
| Topology | Two-level IGBTmade to order: Three-level IGBT |
| Peak efficiency | 98.8%made to order: 98.5% / 99% |
| Grid mode | Grid-formingmade to order: Grid-following |
| THD | < 3% |
| Cooling | Liquid-cooledmade to order: Forced air |
| Ingress protection | IP20 indoormade to order: IP54 outdoor |
| Overload capability | 110% continuousmade to order: 120% for 60 s |
| Reactive power range | -1 to +1 pf |
| Communication | Modbus TCP, CAN, IEC 61850 |
| Black start | Supportedmade to order: Not supported |