Indoor vacuum circuit breaker panel, Titan seriesSample
by Wayanadvajra Panels (Sample) · verified by BARREL
Price on quote
Ordered and invoiced through BARREL — one contract, one GST invoice.
Customise and request quoteMade to order: change the marked specification rows to what you need; Wayanadvajra Panels (Sample) quotes for it.
Or send an open RFQ to every matching merchant.
Wayanadvajra Titan indoor vacuum circuit breaker panel, offered in 4 rating options from 11 kV 2000 A to 33 kV 1250 A. Design: cable chamber with space for CTs and surge arresters, vacuum interrupters with spring-charged stored-energy mechanism and withdrawable truck with service, test and isolated positions. Used by industrial HT incomers, discom 11/33 kV substations and large commercial building HT rooms. Designed and tested to IS 13118, IEC 62271-100 and IEC 62271-200. Lead time 8-10 weeks; delivers to All India. Sample listing: illustrative data for testing BARREL Shop, not a real offer.
- Brand
- Wayanadvajra
- Model
- WAY-B75 series
- Listing type
- Product
- Unit
- nos
- Minimum order
- 2 nos
- Lead time
- 8-10 weeks
- Warranty
- 18 months from supply
- Standards
- IS 13118, IEC 62271-100, IEC 62271-200
- Delivers to
- All India
- GST rate
- 18 %
- Country of origin
- India
- Packaging
- As per item, transit-safe
- Delivery terms
- Ex-works, freight extra at actuals
- Returns
- Replacement of items damaged in transit within 7 days
- Other terms
- Sample data for testing; not a real offer.
Variants
| Variant | Specifications | Min. order · lead time | Price, ex GST |
|---|---|---|---|
| Rating11 kV 2000 AWAY-B75-01 | Rating: 11 kV 2000 A | 2 nos · 8-10 weeks | on quote |
| Rating22 kV 630 AWAY-B75-02 | Rating: 22 kV 630 A | 2 nos · 8-10 weeks | on quote |
| Rating33 kV 630 AWAY-B75-03 | Rating: 33 kV 630 A | 2 nos · 8-10 weeks | on quote |
| Rating33 kV 1250 AWAY-B75-04 | Rating: 33 kV 1250 A | 2 nos · 8-10 weeks | on quote |
Specifications
| Rating | 11 kV 2000 A to 33 kV 1250 A (see variants) |
|---|---|
| Short-circuit rating | 31.5 kA/3 smade to order: 20 kA/3 s / 25 kA/3 s / 40 kA/3 s |
| Construction | Metal-clad withdrawable |
| Breaker operating duty | O-0.3 s-CO-3 min-CO |
| Control voltage | 220 V DCmade to order: 30 V DC / 110 V DC |
| Spring charging motor | 110 V DCmade to order: 230 V AC |
| Protection relay | Numerical feeder protection relaymade to order: Numerical IDMT O/C-E/F relay |
| Busbar material | Aluminium |
| Degree of protection | IP4Xmade to order: IP42 |
| Internal arc classification | Not type-testedmade to order: IAC AFLR 25 kA 1 s |
| Insulation level | 28 kV / 75 kVp |
| Frequency | 50 Hz |
| Panel finish | RAL 7032 powder coatmade to order: RAL 9002 powder coat |