Catalogue / Traction substations & transformers
Booster transformer, Neo seriesSample
by Kakatiya Rail Electrification (Sample) · verified by BARREL
Price on quote
Ordered and invoiced through BARREL — one contract, one GST invoice.
Customise and request quoteMade to order: change the marked specification rows to what you need; Kakatiya Rail Electrification (Sample) quotes for it.
Or send an open RFQ to every matching merchant.
Kakatiya Neo booster transformer, offered in 4 rating options from 20 MVA to 50 MVA. Design: low inrush performance, spares and test support and withstands frequent short-circuits of traction load. Used by port railways, indian Railways TSS and mining railways. Designed and tested to RDSO Specification, IS 2026 and IEC 60076. Lead time 16-20 weeks; delivers to South India. Sample listing: illustrative data for testing BARREL Shop, not a real offer.
- Brand
- Kakatiya
- Model
- KAK-068 series
- Listing type
- Product
- Unit
- nos
- Minimum order
- 1 nos
- Lead time
- 16-20 weeks
- Warranty
- 24 months from commissioning
- Standards
- RDSO Specification, IS 2026, IEC 60076
- Delivers to
- South India
- GST rate
- 18 %
- Country of origin
- India
- Packaging
- Steel skid with shrink wrap
- Delivery terms
- FOR nearest railhead
- Returns
- Returns within 15 days if unused, in original packing
- Other terms
- Sample data for testing; not a real offer.
Variants
| Variant | Specifications | Min. order · lead time | Price, ex GST |
|---|---|---|---|
| Rating20 MVAKAK-068-01 | Rating: 20 MVA | 1 nos · 16-20 weeks | on quote |
| Rating21.6 MVAKAK-068-02 | Rating: 21.6 MVA | 1 nos · 16-20 weeks | on quote |
| Rating30 MVAKAK-068-03 | Rating: 30 MVA | 1 nos · 28-36 weeks | on quote |
| Rating50 MVAKAK-068-04 | Rating: 50 MVA | 1 nos · 28-36 weeks | on quote |
Specifications
| Rating | 20 MVA to 50 MVA (see variants) |
|---|---|
| Primary voltage | 220 kVmade to order: 132 kV / 110 kV |
| Secondary voltage | 27.5 kVmade to order: 2 x 27.5 kV / 55 kV (2x25) |
| Connection | Auto-transformer |
| Cooling | ONAN/ONAFmade to order: ONAN |
| Tap changer | OLTC |
| Overload | 200% for 5 minmade to order: 150% for 15 min |
| Impedance | 10-12% |
| Short-circuit withstand | Per RDSO |
| Insulation | Mineral oil |
| Bushings | Oil to air |
| Protection | Buchholz, OTI, WTI, PRV |
| Noise | < 75 dB(A) |