Catalogue / Traction substations & transformers

No photo yet

Scott-connected traction transformer, Eco 3 seriesSample

by Lumengen Traction Power (Sample) · verified by BARREL

Price on quote

Ordered and invoiced through BARREL — one contract, one GST invoice.

Customise and request quote

Made to order: change the marked specification rows to what you need; Lumengen Traction Power (Sample) quotes for it.

Or send an open RFQ to every matching merchant.

Scott-connected traction transformer from Lumengen, Eco 3 series: 6 rating options between 10 MVA and 50 MVA. Design: heavy overload rating for rolling stock, condition monitoring sensors and spares and test support. Suited to mining railways, indian Railways TSS and industrial sidings. Designed and tested to RDSO Specification, IS 2026 and IEC 60076. Lead time 28-36 weeks; delivers to All India. Sample listing: illustrative data for testing BARREL Shop, not a real offer.

Brand
Lumengen
Model
LUM-D47 series
Listing type
Product
Unit
nos
Minimum order
5 nos
Lead time
28-36 weeks
Warranty
24 months from commissioning
Standards
RDSO Specification, IS 2026, IEC 60076
Delivers to
All India
GST rate
18 %
Country of origin
India
Packaging
Drum / reel with end caps
Delivery terms
Door delivery in metro cities
Returns
No returns on made-to-order items
Other terms
Sample data for testing; not a real offer.

Variants

VariantSpecificationsMin. order · lead timePrice, ex GST
Rating10 MVALUM-D47-01Rating: 10 MVA5 nos · 28-36 weekson quote
Rating16 MVALUM-D47-02Rating: 16 MVA5 nos · 28-36 weekson quote
Rating20 MVALUM-D47-03Rating: 20 MVA5 nos · 28-36 weekson quote
Rating21.6 MVALUM-D47-04Rating: 21.6 MVA5 nos · 28-36 weekson quote
Rating30 MVALUM-D47-05Rating: 30 MVA5 nos · 28-36 weekson quote
Rating50 MVALUM-D47-06Rating: 50 MVA5 nos · 28-36 weekson quote

Specifications

Rating10 MVA to 50 MVA (see variants)
Primary voltage110 kV
Secondary voltage2 x 27.5 kVmade to order: 27.5 kV / 55 kV (2x25)
ConnectionAuto-transformer
CoolingONAN/ONAF
Tap changerOLTC
Overload200% for 5 min
Impedance8-10%made to order: 10-12%
Short-circuit withstandPer RDSO
InsulationMineral oil
BushingsOil to air
ProtectionBuchholz, OTI, WTI, PRV
Noise< 75 dB(A)

BARREL: Bharat Atom Renewable Resources Energy Limited